September 6, 2024 - For food processors that use a dust collection system - the dustiest location in any plant - early smoke detection is critical to quickly suppress potential fires. The challenge is that voluminous dust and particulates from various powders, compounds and processes used in the industry can be confused with some by most traditional, passive, smoke detection systems, which can trigger ongoing alarms. Resolving these alarms often requires excessive troubleshooting and maintenance to keep the system functional. When this is the case, prevalent nuisance alarms may compromise safety.
Although virtually all food processing facilities deal with some level of dust, there is no more daunting environment that illustrates the need for advanced detection systems than inside a dust collection system. Fortunately, even within this dustiest of environments, aspirating smoke detection (ASD) technology can be an effective option.
You may also be interested in:
According to Khaleel Rehman, Director of Development for Honeywell's advanced detection fire team, advanced ASD systems can significantly reduce false alarms and maintenance while increasing safety by detecting smoke at the earliest possible stage via numerous sampling points. The process draws in air through durable piping and analyses it using sophisticated laser-based technology, imaging and photodiodes technology.
Continuous air sampling drawn from the protected area through the pipe network to the sensing unit provides the fastest possible smoke detection rates. In doing so, the system effectively distinguishes between actual smoke and dust or particulates to all but eliminate nuisance alarms. This core technology has been used for decades in sensitive applications such as cleanrooms and data centres where early smoke detection is critical.
Although these systems are quite flexible, many food processing plants use different powders, particulates and processes in varying volumes with unique facility layouts. It is important to consider engaging a partner that can design the system to fit a plant's specific needs.
Extreme dust: a smoke detection and maintenance challenge
One particular production process generates excess powder, which is directed to a dust collection system consisting of large-diameter ducting and paper-based filter media before clean air is vented outdoors.
The dust accumulates quickly and abundantly inside the ducting and can easily overwhelm the filters. This required excessive inspection and frequent maintenance to keep the system fully operational, according to Mike Angstadt, President of Palmetto, Florida-based Flagship Fire Inc, whose company was hired to improve the system's fire safety. The company provides special hazards fire suppression, control and detection solutions for unique, high value industrial assets.
Joseph Albert, Project Manager at Flagship Fire Inc notes, "When technicians would do routine maintenance every few months of sections of ducting, they would bang the sections with a rubber mallet to remove several inches of dust that accumulated inside of this duct work."
According to Angstadt, the dust laden, paper-based filter media would also periodically catch fire when ignited by a stray spark. The plant tase Flagship Fire to improve smoke detection and fire safety within the dust collection system.
"Even though the deflagration index of the dust is low enough that providing explosion protection is not required, the plant sought greater safety with early smoke detection and fire suppression inside the dust collection system," says Angstadt.
As a solution, Flagship Fire specified an ASD system called VESDA-E VEU by Honeywell, a global leader in fire and life safety products. The ASD system draws air samples in a continuous process through holes in durable industrial pipe mounted along the walls and ceiling. The VESDA-E VEU analyses the air in a flair detection chamber that uses a short wavelength laser, a CMOS imager and multiple photodiodes that can distinguish between smoke and dust, minimising false alarms. The system is cross zoned with thermal detectors inside the dust collection filter area.
"With this arrangement, plant operators can manually discharge the high-pressure, CO2 fire suppression agent as needed, or if an incident occurred after hours and no one was present, the plant's VESDA system, cross zoned with thermal device, will automatically discharge to suppress the fire," says Angstadt.
Some minor adjustments were also required to increase system reliability. Since the ASD system draws in air, it does not require direct airflow into the analyser. In fact, too much airflow could affect the results, so Flagship Fire angled the VESDA air sampling points away from the most voluminous air flow sources.
According to Angstadt, the VESDA smoke detection system has performed well since the installation, in conjunction with the thermal device and automatic CO2 fire suppression system. This arrangement has not only minimised false alarms caused by particulates in the dust collection system but also helped improve plant safety by enabling smoke detection at the earliest possible stages of a fire.
Today, when food processors must reduce fire risk in a dust collection apparatus, advanced ASD systems are an effective early warning smoke detection tool that can substantially increase safety while reducing maintenance and nuisance alarms.
For more information contact Dawn Wotapka, Director of External Communications at Honeywell, 715 Peachtree Street, N.E., Atlanta, GA 30308; email: dawn.wotapka@honeywell.com.
The Global MillerThis blog is maintained by The Global Miller staff and is supported by the magazine Milling and Grain
which is published by Perendale Publishers Limited.
No comments:
Post a Comment